4.7 Article

Hybrid Islanding Detection in Microgrid With Multiple Connection Points to Smart Grids Using Fuzzy-Neural Network

期刊

IEEE TRANSACTIONS ON POWER SYSTEMS
卷 32, 期 4, 页码 2640-2651

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2016.2617344

关键词

Hybrid islanding detection; microgrid; multiple connection points; probability of islanding; smart grid

向作者/读者索取更多资源

This paper presents a new hybrid islanding detection approach for microgrids (MGs) with multiple connection points to smart grids (SGs) which is based on the probability of islanding (PoI) calculated at the SG side and sent to the central control for microgrid (CCMG). The PoI values are determined using a combination of passive, active, and communication islanding detection approaches based on the utility signals measured at the SGs sides which are processed by discrete wavelet transform using an artificial neural network (ANN). If PoIANN is larger than the threshold value (indicating high possibility of islanding) then a more accurate approach based on fuzzy network is used to recompute it (PoIFUZZY) where the fuzzy parameters are determined by an adaptive neuro-fuzzy inference system. In the proposed technique, an active islanding is only performed when PoI is high and the amplitudes of the disturb signals are proportional to PoIFUZZY. Furthermore, if the PoI is not correctly received by CCMG, two auxiliary tests will be performed in the MG side to detect islanding. These tests include an intentional passive islanding detection in a short preset time and an active islanding detection with disturb signals proportional to the calculated PoI. Detailed simulations are performed and analyzed to evaluate the performance of the proposed method.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据