期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 32, 期 1, 页码 172-181出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2555844
关键词
Current derivatives; DC microgrid; local measurements; nonunit protection
资金
- Department of Science and Technology, New Delhi, India [DST/EE/20100258]
This paper proposes a nonunit protection scheme for DC microgrids (DC MGs) utilizing only local measurements. This scheme is developed based on the natural characteristics of DC current and its first and second derivatives under fault transients. Since it is based on local measurements, the problems associated with the communication delay are avoided. The selected protection scheme detects and discriminates the faults within a few microseconds of its inception. In this paper, a method to calculate the thresholds, used for the protection scheme, is also discussed. The proposed scheme is validated on a ring-type DC MG architecture under different fault scenarios and tested through MATLAB/Simulink simulations.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐