期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 32, 期 3, 页码 1382-1393出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2574900
关键词
Fault detection; power system protection; traveling waves
资金
- CAPES
- Brazilian National Research Council (CNPq)
This paper proposes a two-terminal traveling-wave-based transmission-line protection using only the first wavefront arrival time at each line terminal (polarity and magnitude of transients are not required), leading to a simple, accurate, and fast protection. In real time, the protection system detects internal and external faults and identifies the fault directionality. In addition, the protection zone and the protection operating time are also formulated. The effects of the sampling rate and the traveling-wave propagation velocity estimation are considered, and some paradigms, such as the need of a high-sampling frequency and an accurate traveling-wave propagation velocity estimation are properly addressed. Two traveling-wave-based protective relays were implemented and evaluated in realistic real-time hardware-in-the-loop simulations considering the communication equipment between the relays, in which reliability and protection operating time could be assessed accordingly.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐