期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 32, 期 1, 页码 536-545出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2585579
关键词
Adaptive protection and control; converter-based distributed generation; multiagent system (MAS); hardware in the loop testing platform
In this paper, a multiagent system-based protection and control scheme is proposed to deal with diverse operation conditions in distribution system due to distributed-generation (DG) integration. Based on cooperation between DG controller and relays, an adaptive protection and control algorithm is designed on converter-based wind turbine DG to limit the influence of infeed fault current. With the consideration of DG control modes, an adaptive relay setting strategy is developed to help protective relays adapt suitable settings to different operation conditions caused by the variations of system topology and DG status. The proposed scheme is tested and validated on a test distribution system in a hardware-in-the-loop real-time testing platform.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐