4.8 Editorial Material

Comments on Impact of Load Frequency Dependence on the NDZ and Performance of the SFS Islanding Detection Method

期刊

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
卷 64, 期 9, 页码 7277-7279

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2017.2696489

关键词

Distributed generation (DG); inverter; islanding detection; Sandia frequency shift (SFS)

资金

  1. Enedis Industrial Chair on Smart Grids research program

向作者/读者索取更多资源

We read with interest an article by Zeineldin and Salama, published in the IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS (vol. 58, no. 1, pp. 139-146, Jan. 2011) and tried to reproduce the results of this article for the needs of our own research. Unfortunately, we were led to think that the load model equations used by the authors contained an inconspicuous but significant mathematical error, leading to erroneous results and conclusion. This letter brings corrections to some figures and their analysis as well as the paper conclusion. The new results show that the load's frequency dependence has actually no significant impact on the NDZ of the SFS method.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据