4.6 Article

Experimental research on spray evaporative cooling system applied to air-cooled chiller condenser

期刊

ENERGY REPORTS
卷 6, 期 -, 页码 906-913

出版社

ELSEVIER
DOI: 10.1016/j.egyr.2020.04.001

关键词

Air-cooled chiller; Evaporative cooling; Spray system; Coefficient of performance

资金

  1. project named Air Cooling Module Unit with Fin Self-cleaning Function Based on Cooling Airflow Spray Cooling key R&D project of Tianjin in 2018 [18YFCZZC00250]

向作者/读者索取更多资源

This study investigates the performance of a refrigeration unit by applying a spray evaporative cooling system to an air-cooled chiller. Experiments are conducted in the temperate monsoon climate region by combining the spray evaporative cooling system with the air-cooled chiller. Moreover, this study adopts a new gas-liquid two-phase swirl nozzle, which is independently developed and characterized by high atomization quality and low energy consumption. The experimental results show that the power of the compressor is reduced, while the COP (Coefficient of Performance) of the air-cooled chiller increases by 4%-8% after the intervention of the spray evaporative cooling system. The spray cooling system contributes to an electricity savings of 2.37%-13.53% in air-cooled chiller systems. If a more reasonable spray evaporative cooling mode is used, such as controlling the water flows according to the cooling capacity and arranging the nozzle positions and angles reasonably, the COP of the air-cooled unit will be further improved. (C) 2020 The Authors. Published by Elsevier Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据