3.8 Proceedings Paper

On the Importance of Tracking the Negative-Sequence Phase-Angle in Three-Phase Inverters with Double Synchronous Reference Frame Current Control

出版社

IEEE
DOI: 10.1109/isie45063.2020.9152442

关键词

Phase-Locked Loop; Negative sequence; double Synchronous Reference Frame; Dual current control; Converter

资金

  1. TKI Wind op Zee under the project Large Offshore Wind Harmonics Mitigation (LOW-HarM) by the Rijksdienst voor Ondernemend, The Netherlands

向作者/读者索取更多资源

A voltage imbalance at the AC terminals of a three-phase inverter creates a ripple in the power signal on the DC side. In order to minimize this ripple, several techniques can be applied, in which a double Synchronous Reference Frame (SRF) current control structure is very typical. In this approach, both the positive and negative sequence currents are controlled. This technique has been shown to have an adequate response against imbalances; however, this paper shows that in the typical implementation of the double SRF control, the output AC pq instantaneous powers will have a constant error due to the phase-angle misalignment of the negative sequence with the positive sequence. Based on mathematical formulations and simulation results, this paper shows that this AC-power error exists, and that it is due to the above reason. In order to overcome this, this paper proposes to have a phase-tracking system that specifically follows the negative sequence phase-angle. The results show that this implementation is able to properly control the output AC power.