3.8 Proceedings Paper

Evaluation of Photovoltaic Inverters Under Balanced and Unbalanced Voltage Phase Angle Jump Conditions

出版社

IEEE
DOI: 10.1109/pvsc45281.2020.9300604

关键词

photovoltaic inverter; hardware-in-the-loop; IEEE Std 1547.1; phase jump; ride-through

资金

  1. U.S. Department of Energy's National Nuclear Security Administration [DE-NA-0003525]
  2. Natural Resources Canada (NRCan) through the Program on Energy Research and Development (PERD)

向作者/读者索取更多资源

In 2016, 1.2 GW of photovoltaic (PV) power tripped off in California during the Blue Cut Fire when PV inverters miscalculated the grid frequency during a line-to-line fault. In response, the 2018 edition of the IEEE 1547 interconnection standard was updated to mandate distributed energy resource (DER) devices ride-through voltage phase angle changes that appear during faults. This new requirement is designed to ensure bulk-system stability is not impacted by emergent DER misbehaviors triggered by local fault events. Transitory DER behaviors under phase changes may still significantly impact grid operations, so it is necessary to quantify the DER response to both balanced and unbalanced voltage phase angle shifts. To achieve this, two PV inverters were subjected to balanced and unbalanced phase jump changes defined in the IEEE 1547.1-2020 test protocol to validate compliance to IEEE 1547. Experimental results show that one DER inverter was compliant to IEEE 1547 and its momentary cessation behavior produced stable power system response. However, the other PV inverter failed the IEEE 1547.1 compliance test and tripped off during some of the phase jump experiments.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据