Utilization of U-shaped finned heat pipe heat exchanger in energy-efficient HVAC systems

期刊

出版社

ELSEVIER
DOI: 10.1016/j.tsep.2021.100984

关键词

U-shaped heat-pipe; Coefficient of performance; Energy recovery; Dehumidification

资金

  1. Directorate of Research and Development Universitas Indonesia

向作者/读者索取更多资源

This study investigates the utilization of a finned U-shaped heat pipe heat exchanger in a vertical configuration to reduce cooling and reheating energy in an HVAC system. Results show that the two-row U-shaped HPHE significantly affects precooling and reheating, enhancing the COP by 39.9% and reducing relative humidity by 21.6%.
Energy-efficient Heating Ventilating and Air Conditioning (HVAC) system utilization is necessary to reduce energy consumption in buildings amid the supply difficulties of energy sources and the environmental impacts of high energy use. This study aims to investigate the utilization of a finned U-shaped heat pipe heat exchanger (HPHE) in a vertical configuration to reduce cooling and reheating energy in an HVAC system. The effectiveness of the U-shaped HPHE, coefficient of performance (COP) of the HVAC system coupled with U-shaped HPHE, and dehumidification capability are presented in this paper. The U-shaped HPHE was installed at the inlet fresh airstream ducts wrapped around the cooling coil, and tests were carried out with one-and two-row configurations arranged in eight heat pipes per row. The fresh air temperature and velocity across the evaporator section were varied at the ranges from 30 to 45 degrees C and 1.5 to 2.5 m/s, respectively. The results show that the two-row U-shaped HPHE significantly affects the precooling and reheating processes in the HVAC system compared with the one-row configuration. The two-row U-shaped HPHE can enhance the coefficient of performance (COP) by 39.9% over the HVAC without HPHE. The highest energy saving for precooling and reheating was 288.1 and 340.2 W, respectively, at 0.080 m(3)/s air volume and can reduce relative humidity by 21.6%. The investigation implies that the U-shaped heat pipe succeeded in becoming a solution to an HVAC system that requires cooling to reheat the HVAC system.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据