4.7 Article

Energetic, exergetic and financial evaluation of a solar driven absorption chiller - A dynamic approach

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 137, 期 -, 页码 34-48

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2017.01.041

关键词

Solar cooling; ETC; Exergetic analysis; Financial analysis; Dynamic simulation

资金

  1. Onassis Foundation

向作者/读者索取更多资源

In this study, a solar cooling system of 100 kW is analyzed parametrically in dynamic basis for the city of Athens, Greece. The objective of this study is the design of a sustainable system, using energetic, exergetic and financial criteria. The examined system includes evacuated tube collectors, storage tank and a single stage absorption chiller operating with LiBr-H2O working pair. Different combinations of collecting areas and storage tank volumes are tested in order to determine the most suitable cases exergetically. These optimum cases are evaluated financially and finally the system with the higher financial indexes is selected as the most suitable. More specifically, the collecting area is analyzed from 150 m(2) to 600 m(2) and the storage tank from 6 m(3) to 16 m(3). Finally, 450 m(2) of evacuated tube collectors with a 14 m(3) storage tank was proved to be the optimum solution financially with 15 years payback period and 67 k epsilon net present value. (c) 2017 Elsevier Ltd. All rights reserved.