4.7 Article

Energetic, Exergetic, Economic and Environmental (4E) analysis of a solar assisted refrigeration system for various operating scenarios

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 148, 期 -, 页码 1055-1069

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2017.06.063

关键词

Solar refrigeration; Absorption-compression cascade system; Absorption chiller; Exergetic analysis; VCC

向作者/读者索取更多资源

The objective of this work is to investigate the yearly performance an absorption-compression cascade refrigeration system driven by solar energy. Different operating scenarios are examined by testing different combinations of refrigeration and condensation temperatures. Evacuated tube collectors coupled to a storage tank are selected to be used for feeding the refrigeration system with the proper heat demand. LiBr-H2O and R134a are selected as working pair in the absorption cycle and refrigerant in the compression cycle respectively. The analysis is performed in energetic, exergetic, economic and environmental terms with a developed and validated model in EES (Engineering Equation Solver). According to the final results, the cascade system, in cases with low refrigeration temperatures is better economically while in higher refrigeration temperatures presents the greater percentage of electricity savings. On the other hand, higher heat rejection temperature leads both to higher economic indexes and to higher electricity savings. For the case of heat rejection at 40 degrees C and refrigeration at -20 degrees C, the electricity savings are found 53.98%, the IRR 6.6% and the payback period close to 14 years. (C) 2017 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据