Estimating the maximum energy-saving potential based on IT load and IT load shifting

期刊

ENERGY
卷 138, 期 -, 页码 902-909

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.energy.2017.07.092

关键词

Data center; Energy-saving; Demand response; Dynamic IT load; IT load shifting

资金

  1. Chinese National Science Foundation [51376137]

向作者/读者索取更多资源

Cooling system consumes more than 35% of total electricity in most data centers. The provided cooling normally exceeds the actual demand of IT equipment in order to assure the safe operation, resulting in a low energy efficiency. In this paper, a novel method based on demand response was proposed to precisely control the cooling supply, and the energy saving potential was assessed systematically. Compared to the reference case, in which the cooling demand is determined by assuming all of servers are in the running status, when the cooling demand was determined based on the measured dynamic IT load at room level, row level, rack level and server level, it can be reduced by 7.9%, 14.2%, 15.6% and 17.9% respectively for the random selected 48 h. In addition, IT load shifting also has a big potential to save energy, as it can make the cooling system working at a higher energy efficiency, which varies with loads. Two cases were studied: even distribution of IT load and optimized IT load shifting. Compared to the best case that determines the cooling demand according to the IT load at server level, they can further reduce the electricity consumption of cooling systems by 0.9%, and 1.2%. (C) 2017 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据