4.5 Article

An Improved Commutation Prediction Algorithm to Mitigate Commutation Failure in High Voltage Direct Current

期刊

ENERGIES
卷 10, 期 10, 页码 -

出版社

MDPI AG
DOI: 10.3390/en10101481

关键词

commutation failure prevention (CFPREV); high voltage direct current (HVDC); inrush current; harmonic detection; predictive control

资金

  1. science and technology project of the State Grid Corporation of China [FX71-16-003, XT71-15-045]

向作者/读者索取更多资源

Commutation failure is a common fault for line-commutated converters in the inverter. To reduce the possibility of commutation failure, many prediction algorithms based on alternating current (AC) voltage detection have already been implemented in high voltage direct current (HVDC) control and protection systems. Nevertheless, there are currently no effective methods to prevent commutation failure due to transformer excitation surge current. In this paper, an improved commutation failure prediction algorithm based on the harmonic characteristics of the converter bus voltage during transformer charging is proposed. Meanwhile, a sliding-window iterative algorithm of discrete Fourier transformation (DFT) is developed for detecting the voltage harmonic in real time. This method is proved to be an effective solution, which prevents commutation failure in cases of excitation surge current, through experimental analysis. This method is already implemented into TianShan-ZhongZhou (TianZhong) +/- 800 kV ultra high voltage direct current (UHVDC) system.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据