4.5 Article

Modeling of HVDC System to Improve Estimation of Transient DC Current and Voltages for AC Line-to-Ground FaultAn Actual Case Study in Korea

期刊

ENERGIES
卷 10, 期 10, 页码 -

出版社

MDPI
DOI: 10.3390/en10101543

关键词

AC line-to-ground fault; estimation of dynamic variations in DC voltage and current; Jeju-Haenam HVDC system; PSS/E simulation environment

资金

  1. Electric Power Public Tasks Evaluation & Planning Center (ETEP) - Korea government Ministry of Trade, Industry Energy (MOTIE) [70300037]
  2. Korea Evaluation Institute of Industrial Technology (KEIT) [70300037] Funding Source: Korea Institute of Science & Technology Information (KISTI), National Science & Technology Information Service (NTIS)

向作者/读者索取更多资源

A new modeling method for high voltage direct current (HVDC) systems and associated controllers is presented for the power system simulator for engineering (PSS/E) simulation environment. The aim is to improve the estimation of the transient DC voltage and current in the event of an AC line-to-ground fault. The proposed method consists primary of three interconnected modules for (a) equation conversion; (b) control-mode selection; and (c) DC-line modeling. Simulation case studies were carried out using PSS/E and a power systems computer aided design/electromagnetic transients including DC (PSCAD/EMTDC) model of the Jeju-Haenam HVDC system in Korea. The simulation results are compared with actual operational data and the PSCAD/EMTDC simulation results for an HVDC system during single-phase and three-phase line-to-ground faults, respectively. These comparisons show that the proposed PSS/E modeling method results in the improved estimation of the dynamic variation in the DC voltage and current in the event of an AC network fault, with significant gains in computational efficiency, making it suitable for real-time analysis of HVDC systems.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据