4.7 Article

Phasor Measurement Unit With Digital Inputs: Synchronization and Interoperability Issues

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIM.2022.3175052

关键词

Phasor measurement units; Synchronization; IEC Standards; Clocks; Interoperability; Substations; Protocols; Digital substation; IEC 61850; interoperability; phasor measurement unit (PMU); sampled value (SV); synchronization; time quality

资金

  1. European Metrology Programme for Innovation and Research (EMPIR) - European Union [17IND06]

向作者/读者索取更多资源

In recent years, electrical substations have been transitioning toward a fully digital measurement infrastructure, using the IEC Std 61850-9-2 defined sampled value (SV) data format. This article presents the design and development of a stand-alone PMU based on digital inputs, which has been characterized in terms of estimation accuracy and enriched with a new functionality to monitor the time quality of the SV data stream. The results confirm the potential of SV-based PMUs and suggest further enhancement for synchrophasor measurements based on digital inputs only.
In recent years, electrical substations are experiencing a rapid transition toward a fully digital measurement infrastructure in terms of data acquisition, storage, and processing. The IEC Std 61850-9-2 defines the data format, also known as sampled value (SV), to be employed by instrument transformers, merging units, and controller devices. In this scenario, it is reasonable to expect that the phasor measurement units (PMUs) will be directly connected with digital instrument transformers and will be required to process directly the SV data stream. In this article, we present the design and development of a stand-alone PMU based on digital inputs. The prototype has been characterized in terms of estimation accuracy and enriched with a novel functionality that allows for monitoring the time quality of the SV data stream. In this way, the device truly becomes an intelligent electronic device (IED) that guarantees higher interoperability and a more robust management of sporadic synchronization issues. The proposed results confirm the potential of SV-based PMUs and highlight the possibility of further enhancement for synchrophasor measurements based on digital inputs only.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据