4.8 Article

DC Bias Content Extraction of Power Transformer Under AC and DC Environment and its Suppression Measures

期刊

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2023.3303633

关键词

Bias voltage detection; dc bias; excitation current; transformer

向作者/读者索取更多资源

This article proposes a method for measuring the bias voltage of transformers to detect TDB, which has been verified through experiments. It also designs simulated experiments and suppression methods for TDB, providing references for TDB control.
The phenomenon of transformer dc bias (TDB) will saturate the transformer core, resulting in the local overheating, accelerating the ageing of insulating material, and even affecting the transformer safe operation. Therefore, it is of great significance to carry out the TDB detection and suppression. In this article, first, according to the distortion characteristics of the transformer excitation current under TDB. This article presents a method for measuring the bias voltage content of the transformer in the ac/dc environment to detect TDB. Second, the value of TDB is calculated by measuring the voltage difference before and after the dc bias, so as to obtain the degree of TDB. The feasibility of this scheme is verified by multigroup simulations of single-phase transformer (SPT) and three-phase transformer (TPT). Finally, the SPT and TPT simulated experiments of TDB are designed, and one kind of TDB suppression is carried out based on a hybrid transformer model. The experimental results are in good agreement with the simulation results, which can provide certain reference for TDB control in the dc transmission and ac/dc distribution networks.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据