4.8 Article

Effect of inactive section on cooling performance of compressive elastocaloric refrigeration prototype

期刊

APPLIED ENERGY
卷 351, 期 -, 页码 -

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2023.121839

关键词

Elastocaloric; NiTi tube; Inactive section; Cooling performance enhancement; Cyclic compression

向作者/读者索取更多资源

This study reveals the negative impact of the inactive section in compressive elastocaloric refrigeration systems on the specific cooling power (SCP). Numerical simulations and experiments show that reducing the volume ratio of the inactive section can significantly improve SCP.
Elastocaloric (eC) cooling using shape memory alloy (SMA) with zero direct carbon emission is a promising alternative of traditional vapor-compression technology. Compressive eC refrigeration prototype (ERP) performs high fatigue life but suffers from the limited cooling performance. Many studies focus on enhancing the heat transfer property of compressive eC regenerators to improve the specific cooling power (SCP). However, reducing the SCP loss is also essential for developing high-cooling-performance compressive ERPs but has not been given sufficient attention. In this study, we revealed that the force holder widely used in compressive ERPs works as an inactive section that dramatically reduce the SCP produced by the NiTi SMA active section. Numerical heat transfer simulations and experiments were conducted to study the impact of the inactive section on the SCP at varied operation parameters. Nondimensionalized governing equations of the numerical model revealed that the volume ratio (Vol(non)) of the fluid channel of the inactive section to that of the active section is the determinant geometric parameter for the SCP decrease. Numerical results show that, larger operation frequency f(ERP), smaller dimensionless fluid velocity V* and system temperature span (Delta T-span) lead to more pronounced decreases in SCPnon (ratio of the SCP to ideal SCPideal at Vol(non) = 0) as the Vol(non) increases. It also indicates that the Vol(non) should be minimized to better < 0.08 for achieving excellent SCPnon > 0.95. Experiments validate that the regenerator with a reduced Vol(non) = 0.08 exhibits a notable increase of 30.8% and 66.7% in zero-Delta T-span SCP and no-load Delta T-span respectively, in comparison to the regenerator with Vol(non) = 0.5. Therefore, minimizing the Vol(non) of the inactive section via reducing the length and diameter of the fluid channel inside the force holder is necessary and highly recommended for developing high-performance compressive ERPs.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据