Experimental study of refrigerant condensation heat transfer and pressure drop in horizontal tubes with full and partial coiled wire inserts (CWIs)

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2023.124577

关键词

Condensation; Heat transfer coefficient (HTC); Pressure drop; Coiled wire insert (CWI)

向作者/读者索取更多资源

The experimental investigation focused on the HTC and pressure loss in horizontal smooth and wire-inserted tubes. Three different coiled wire inserts (CWIs) with varying lengths and thicknesses were studied. The results showed that the use of CWIs significantly improved the HTC compared to smooth tubes. New correlations were developed to accurately predict the condensation HTC in smooth and wire-inserted tubes.
The condensation heat transfer coefficient (HTC) and pressure loss in the horizontal smooth and wire-inserted tubes were investigated experimentally. Three different coiled wire inserts (CWIs) of the full length of 1000 mm and partial lengths of 100 mm and 200 mm with 0.8 mm wire thickness and 9.5 mm pitch were studied. The main condenser was a heat exchanger of double pipe type with an 8 mm inner diameter for the refrigerant and an active length of 1 m cooled by water circulating in the annulus. The experiments were conducted for different refrigerant mass velocities within 90-400 kg/m2s and low vapor mass fraction (x < 0.3). The findings revealed that using 1000 mm (full-length), 200 mm, and 100 mm length CWIs improved the HTC by 95%, 40%, and 18%, respectively, over the smooth tube. The HTC per unit pressure drop was also evaluated to assess the performance of full and partial CWIs. The results showed that the HTC per unit pressure loss decreases for all tubes as the mass velocity increases. In addition, the performance of the tubes with CWIs approached that of the smooth tube at higher mass velocities. The ratios of HTC per unit pressure drop at higher mass fluxes for full-length, 200 mm, and 100 mm length CWIs to that of the smooth tube were about 0.4, 0.78, and 0.9, respectively. Although the pressure drop increased almost linearly with the partial CWI length, the HTC increased sharply for the small inserts and gradually for the larger insert lengths. The results obtained for the condensation HTC in smooth and full wire-inserted tubes were also compared with the estimations of well-known correlations in the literature. Furthermore, three new correlations were developed to predict condensation HTC in smooth tubes and tubes with full and partial CWIs. It was shown that the new correlations are more accurate than the available ones.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据