4.6 Article

Assessment of the Minimum Sampling Frequency to Avoid Measurement Redundancy in Microclimate Field Surveys in Museum Buildings

期刊

SENSORS
卷 16, 期 8, 页码 -

出版社

MDPI
DOI: 10.3390/s16081291

关键词

temperature and relative humidity; sampling rate; museum measurements; indoor microclimate; Sorolla paintings; Pio V Museum

资金

  1. MINECO [HAR2013-47895-C2-1-P, HAR2013-47895-C2-2-P]
  2. Sapienza Universita di Roma

向作者/读者索取更多资源

Monitoring temperature and relative humidity of the environment to which artefacts are exposed is fundamental in preventive conservation studies. The common approach in setting measuring instruments is the choice of a high sampling rate to detect short fluctuations and increase the accuracy of statistical analysis. However, in recent cultural heritage standards the evaluation of variability is based on moving average and short fluctuations and therefore massive acquisition of data in slowly-changing indoor environments could end up being redundant. In this research, the sampling frequency to set a datalogger in a museum room and inside a microclimate frame is investigated by comparing the outcomes obtained from datasheets associated with different sampling conditions. Thermo-hygrometric data collected in the Sorolla room of the Pio V Museum of Valencia (Spain) were used and the widely consulted recommendations issued in UNI 10829:1999 and EN 15757:2010 standards and in the American Society of Heating, Air-Conditioning and Refrigerating Engineers (ASHRAE) guidelines were applied. Hourly sampling proved effective in obtaining highly reliable results. Furthermore, it was found that in some instances daily means of data sampled every hour can lead to the same conclusions as those of high frequency. This allows us to improve data logging design and manageability of the resulting datasheets.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据