4.7 Review

Double skin facades (DSF) and building integrated photovoltaics (BIPV): A review of configurations and heat transfer characteristics

期刊

RENEWABLE ENERGY
卷 89, 期 -, 页码 743-756

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.renene.2015.12.043

关键词

BIPV; BIPV/T; DSSF; DSVF; PV; Solar facades

资金

  1. EU [296016]

向作者/读者索取更多资源

This article presents the state of the knowledge on the thermal analysis of double skin facades with integrated photovoltaic (PV) panels called the Building Integrated Photovoltaics (BIPV) in terms of the published studies carried out on these systems. The idea of integration of the PV panels by replacing building elements, increase the prospects of the renewable energy systems. Taking also into account the need to use more renewable energy systems in buildings, the investigation of the BIPV systems to improve their performance is of a great importance. The literature studies are separated into experimental and theoretical for naturally ventilated systems and mechanically ventilated with external means e.g. fan use. It is concluded that most researchers studied the systems with mechanical ventilation rather than the systems with natural ventilation because the latter are more complex in terms of the air flow behaviour in the air duct. Additionally, various researchers proposed Nu number correlations and convective heat transfer correlation under several assumptions and conditions every time, for different range or Ra number which are presented and compared in this paper. (C) 2015 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据