Application of STATCOM-supercapacitor for low-voltage ride-through capability in DFIG-based wind farm

期刊

NEURAL COMPUTING & APPLICATIONS
卷 28, 期 9, 页码 2665-2674

出版社

SPRINGER LONDON LTD
DOI: 10.1007/s00521-016-2219-6

关键词

Doubly fed induction generator (DFIG); Static synchronous compensator (STATCOM); Supercapacitor; Symmetric and asymmetric fault

向作者/读者索取更多资源

Low-voltage problem emerges in cases of symmetrical and asymmetrical fault in power systems. This problem can be solved out by ensuring low-voltage ride-through capability of wind power plants, through a static synchronous compensator (STATCOM). The purpose of this study is to reveal that the system can be recovered well by inserting a STATCOM with energy storage to a bus where a double-fed induction generator (DFIG)-based wind farm has been connected, so the bus voltage is maintained within desired limits during a fault. Moreover, a supercapacitor is used as an energy storage element. Modeling of the DFIG and STATCOM along with the nonlinear supercapacitor was carried out in a MATLAB/Simulink environment. The behaviors of the system under three- and two-phase faults have been compared with and without STATCOM-supercapacitor, by observing the parameters of DFIG output voltage, active power, speed, electrical torque variations, and d-q axis stator current variations. It was found that the system became stable in a short time when the STATCOM-supercapacitor was incorporated into the full-order modeled DFIG.