4.5 Article

Assessment of natural ventilation strategy to decrease the risk of COVID 19 infection at a rural elementary school

期刊

HELIYON
卷 9, 期 7, 页码 -

出版社

CELL PRESS
DOI: 10.1016/j.heliyon.2023.e18271

关键词

Natural ventilation; Low-cost ventilation strategy; Covid19; ACH; DecayCO2 concentration method; Thermal comfort

向作者/读者索取更多资源

This study investigates the natural ventilation in a rural elementary school and its impact on thermal comfort and infection risk. The results show that the school has good natural ventilation, with temperature and humidity meeting regulatory requirements and low infection risk.
Natural ventilation in low-budget elementary schools is the main focus to ensure the health and comfort of its occupants, specifically when looking at the global pandemic related to SARS-COV2. This paper presents an experimental and novel study of natural ventilation in a public elementary school (Los Zumacales), with a particularly low economic budget. The study was carried out during the winter months of the Covid 19 pandemic. The school is located in the rural area of Castilla y Le & PRIME;on (North-Western Spain) far from high traffic roads. In this study, a methodology of measuring CO2 concentration was applied in nine classrooms in a school. The experimental study shows the level of natural ventilation in each classroom, expressed in Air Changes per Hour (ACH), using the Decay CO2 concentration method. The method is proven by comparing the experimental values of the obtained ACH with those determined by the most powerful methods to achieve appropriate ventilation levels. Thus, ensuring health protection protocol in rural schools, against the COVID 19 pandemic. Harvard guide and Spanish regulations (RITE), two widely recognized methods have been used together with the experimentally obtained standard by Rey et al. Only one classroom showed a value lower than 3 indicating poor ventilation. In this study, the degree of thermal comfort in the nine classrooms were also analyzed according to the EN15251 standard. An average indoor temperature of approximately 19 degrees C was obtained, and the relative humidity was stable and correct according to Spanish regulations. In addition, the risk of infection in each classroom was estimated following the international method recommended by the federation of European Heating, Ventilation, and Air Conditioning Associations (REHVA). The probability of infection in all the cases studied was less than 14%. Therefore, this study provides a strong response against infections illnesses, such as Covid 19, in educational buildings where economic budgets of their facilities are low in both, maintenance and investment.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据