Air infiltration and related building energy consumption: A case study of office buildings in Changsha, China

期刊

JOURNAL OF BUILDING ENGINEERING
卷 74, 期 -, 页码 -

出版社

ELSEVIER
DOI: 10.1016/j.jobe.2023.106859

关键词

Airtightness Tracer gas method; Air-conditioning system; EnergyPlus Infiltration-related energy consumption

向作者/读者索取更多资源

Previous studies have shown that the air infiltration in buildings and its impact on indoor environment and energy consumption are influenced by climate characteristics. However, there is limited information available for buildings in southern China, where the building design traditionally emphasizes openness and shading. This study investigates the airtightness and energy consumption in a Hot Summer and Cold Winter climate region of southern China using measurements and simulations.
Past studies reveal that air infiltration through the building envelope and its impact on the indoor environment and energy consumption are significantly influenced by climate characteristics. However, little relevant information is available for buildings in southern China, where the building design traditionally follows a philosophy of being open and shaded. The present study employs both experimental measurements and numerical simulations to investigate the airtightness of buildings in Hot Summer and Cold Winter (HSCW) climate region of southern China and the associated energy consumption. The measurements and simulations are based on a typical office building in Changsha. Measurement results show that the air infiltration rate of six tested spaces at the natural pressure difference ranges from 0.10 to 0.30 h (1) with an average of 0.17 h (-1) in summer, and from 0.09 to 0.32 h (-1) with an average of 0.16 h (-1) in winter. The operation of the air-conditioning system affects largely air infiltration, and each unit change in setpoint air temperature can result in an average of one-third or more change in air infiltration rate. Simulation results show that a decrease in air infiltration rate from 0.17 h (-1) to 0.01 h (-1) reduces the infiltration-related cooling energy consumption from 14.29 to 0.75 kWh/m(2)center dot year and heating energy consumption from 8.20 to 0.39 kWh/m(2)center dot year. The same change in the setpoint air temperature of air-conditioning system in summer and winter results in different infiltrationrelated energy consumption. The findings would contribute to an improved energy simulation and assessment of buildings in southern China.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据