4.7 Article

Stability and multi-frequency dynamic characteristics of nonlinear grid-connected pumped storage-wind power interconnection system

期刊

NONLINEAR DYNAMICS
卷 -, 期 -, 页码 -

出版社

SPRINGER
DOI: 10.1007/s11071-023-08942-5

关键词

Pumped storage-wind power interconnection system; Stability; Multi-frequency dynamic characteristics; Hopf bifurcation; Capacity ratio

向作者/读者索取更多资源

This paper investigates the stability and multi-frequency dynamic characteristics of nonlinear grid-connected pumped storage-wind power interconnection system (PS-WPIS). The study establishes a nonlinear model, analyzes stable domain and dynamic response, explains the coupling mechanism, and studies the effects of various parameters. The results reveal the characteristics of the system, such as the stable domain, multi-frequency oscillations, and the impact of capacity ratio on stability.
This paper researches the stability and multi-frequency dynamic characteristics of nonlinear grid-connected pumped storage-wind power interconnection system (PS-WPIS). Firstly, a nonlinear model of grid-connected PS-WPIS is established. Then, the system stability and multi-frequency characteristics are revealed through stable domain and dynamic response analysis. Furthermore, the coupling mechanism of grid-connected PS-WPIS is explained, and the effect of capacity ratio on system stability is studied. Finally, the effect of hydraulic, mechanical and electrical parameters on grid-connected PS-WPIS is revealed. The results show that the stable domain of grid-connected PS-WPIS consists of two horizontal bifurcation lines and one curving bifurcation line. The former is related to wind power subsystem, and the latter is related to pumped storage subsystem. The grid-connected PS-WPIS contains the phenomenon of multi-frequency oscillations. The multi-frequency oscillations are generated by the coupling effect of pumped storage subsystem and wind power subsystem. The capacity increase of pumped storage or wind power worsens the stability and dynamic response of grid-connected PS-WPIS. The regulation performance of grid-connected PS-WPIS can be significantly improved by selecting smaller values of flow inertia time constant of penstock and time constant of wind turbine shafting.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据