4.6 Article

Precise PMU-Based Localization and Classification of Short-Circuit Faults in Power Distribution Systems

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 38, 期 5, 页码 3262-3273

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2023.3268767

关键词

Fault classification; fault localization; phasor measurement unit (PMU)

向作者/读者索取更多资源

This paper presents a PMU-based method for fault localization and classification, which introduces the concept of a virtual bus to accurately determine the fault location and a generic fault model for fault classification. The effectiveness of the proposed approach is verified through simulation using a real-time digital simulator and sensitivity analysis.
Knowing the exact location of a short-circuit fault in a power distribution system (PDS) is essential for rapid restoration of service to customers and has a direct impact on the operational costs and reliability of the system. In this paper a phasor measurement unit (PMU) based method for fault localization and classification is presented. By introducing the concept of a virtual bus, the exact fault location on the line is determined rather than just a bus closest to the fault. Moreover, after determining the fault location, a generic fault model (GFM) is introduced to classify the type of fault by solving a minimization problem, which also provides fault impedances as a result. These can then be further used to determine if the fault occurred on the lateral instead of the main feeder without using additional PMU at the end of that lateral. The effectiveness of the proposed approach is verified by simulating various fault scenarios in two test systems based on real PDSs using a real-time digital simulator. In addition, a sensitivity analysis of the method is performed for different noise levels in the input parameters to verify its applicability to the real system.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据