期刊
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY
卷 -, 期 -, 页码 -出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TEMC.2023.3276770
关键词
Grounding grid; lightning; secondary cable; transient disturbance
In this article, the author develops a grounding grid circuit model that takes into account the mutual inductance between the secondary cable and the ground conductor. A circuit model of the secondary cable is also established, considering the uneven ground potential distribution and the mutual inductance between the cable and the ground conductor. The two models are then unified to calculate the transient disturbance in the secondary cable caused by a lightning strike on the grounding grid. The feasibility of the method is verified through experiments, and the effect of the ground potential difference and mutual induction between the cable and the grid is analyzed. The results show that both the mutual inductance and the uneven ground potential distribution greatly affect the transient disturbance in the secondary cable.
When a substation suffers from a lightning strike, beside the interference from the space, there are two main ways in which the transient disturbance affects the secondary cable through the grounding system: the uneven potential distribution and the mutual inductance between the secondary cable and the ground conductor. In this article, a circuit model of grounding grid is developed taking into consideration the mutual inductance between the secondary cable and the ground conductor. While a circuit model of the secondary cable is established with the consideration of uneven ground potential distribution and the mutual inductance between the secondary cable and the ground conductor. Then, the two models are unified to calculate the transient disturbance in the secondary cable due to a lightning strike on the grounding grid. The feasibility of the method is verified through experiments. Then, the effect of the ground potential difference of the grounding grid and its mutual induction with the cable is analyzed. The results show that both the mutual inductance between the cable and the grid and the uneven ground potential distribution greatly affect the transient disturbance in secondary cable.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据