Performance measurement of a smoke extraction system for buildings in full-scale hot smoke test

期刊

MEASUREMENT
卷 93, 期 -, 页码 340-350

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.measurement.2016.07.040

关键词

Smoke extraction system; Hot smoke test; Smoke layer; Plugholing; Makeup air

资金

  1. Ministry of Science and Technology - Taiwan [NSC 101-2221-E-274-004]

向作者/读者索取更多资源

The current inspection method for a smoke extraction system in Taiwan measures whether the air flow of the smoke vent conforms to the design value. However, this method is inapplicable to natural smoke extraction systems. As the plugholing effect is disregarded, adequate air flow cannot ensure that the system will exhaust smoke effectively during a fire. Hence, a full-scale hot smoke test for smoke extraction systems is necessary. Some international test criteria are formulated using visible smoke and alcoholic fuel which is pollution-free after combustion. The effectiveness is judged only by visually observing the smoke's flow direction, which is indeed unscientific. This study used a string of vertical smoke layer measuring instruments composed of several approved photoelectric smoke detectors, as well as a light attenuation measuring device composed of illuminance meters to conduct tests on the effect of makeup air. The results proved that the former one uses different height induction times to judge the position of the smoke layer effectively, while the latter one uses the light attenuation rate to distinguish the smoke density instantly and accurately. The obtained experimental data were consistent with the onsite smoke distribution. The two sets of equipment designed in this study can be used for full-scale hot smoke tests to obtain performance data for a smoke extraction system. (C) 2016 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据