Fault Detection in DC Microgrid: A Transient Monitoring Function-Based Method

期刊

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
卷 70, 期 6, 页码 6284-6294

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2022.3194580

关键词

Fault detection; Estimation; Current measurement; Indexes; Fault diagnosis; Transient analysis; Monitoring; Detection method for dc microgrid (DCMG); fault detection; modal transformation; Teager-Kaiser energy operator (TKEO); transient function monitoring

向作者/读者索取更多资源

This article proposes a fault detection method for dc microgrids (DCMGs) based on the transient monitoring function (TMF). The method utilizes modal components of the measured currents and estimates the modal current using TMF concept. A residual signal is defined as the absolute difference between the modal and estimated currents, which exhibits significant variations after a fault occurrence. The Teager-Kaiser energy operator is then applied to amplify the changes, followed by a fault detection index (FDI) to reveal the fault and distinguish faulty conditions in different operation modes of DCMGs.
This article develops a transient monitoring function (TMF) based fault detection method for dc microgrids (DCMGs). In this method, the measured currents from one-end of the poles are first transformed into modal components. Then, the modal current is estimated using TMF concept. Afterward, the residual signal is defined as the absolute value of the difference between the modal and estimated currents. This signal has negligible fluctuations during the normal operation, while it experiences significant variations after fault occurrence. This feature is selected to reflect the fault incidence. To do so, the Teager-Kaiser energy operator is applied to the residual signal to amplify the changes, followed by a fault detection index (FDI). Comparing FDI with a threshold can reveal the fault. Furthermore, FDI can discriminate the faulty conditions in different operation modes of DCMG with a wide variation of fault conditions. To assess the developed scheme performance, a DCMG with different kinds of sources and loads is simulated in MATLAB/Simulink. The results confirm the quickness and the high accuracy of the proposed technique. Moreover, the method is validated in an experimental laboratory small-scale test bench. Finally, to demonstrate the superiority of the method, a comparative study with recent methods is presented.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据