4.5 Article

Surface Flashover Characteristics of the 252-kV Conical Insulator in C4F7N/CO2 Gas Mixture

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TDEI.2023.3249653

关键词

Insulators; Discharges (electric); Flashover; Voltage; Surface discharges; Conductors; Lightning; Breakdown; CO2; quasi-uniform field; surface flashover

向作者/读者索取更多资源

This article investigates the surface flashover characteristics of a 252-kV conical insulator in a C4F7N/CO2 mixture, an alternative to SF6. The study shows that adding small amounts of C4F7N to CO2 can increase the surface flashover voltage. The experiment also observes four types of discharge traces, most of which are on the concave side under both ac and LI voltage. The polarity effect is noticed in C4F7N/CO2 gas mixtures, and a formula is fitted to predict the flashover voltage.
This article reports on an investigation into the surface flashover characteristics of the 252-kV conical insulator in a C4F7N/CO2 mixture, which is used as an alternative to sulphur hexafluoride (SF6). This study was done for a quasi-uniform field using a 252-kV experimental platform. The influence of molar fraction and gas pressure is reported and compared to that in SF6. Results show that small quantities of C4F7N mixed in CO2 can increase the surface flashover voltage. Four types of discharge traces are observed in the experiment, and most traces are on the concave side under both ac and lightning impulse (LI) voltage. The polarity effect is observed in C4F7N/CO2 gas mixtures. An empirical formula is fitted for C4F7N/CO2 mixtures by experimental data under LI(-), and 0.7-MPa 9%C4F7N/91%CO2 mixture has great potential to replace 0.5-MPa SF6.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据