4.5 Article

Dynamic Investigation of a Coupled Parabolic Trough Collector-Phase Change Material Tank for Solar Cooling Process in Arid Climates

期刊

ENERGIES
卷 16, 期 10, 页码 -

出版社

MDPI
DOI: 10.3390/en16104235

关键词

parabolic trough collector; double-effect absorption chiller; phase change material; solar-powered cooling

向作者/读者索取更多资源

This study investigates the feasibility and potential of a solar-powered cooling system with parabolic trough collectors and a phase change material tank in arid climates. The results show that the 240 m(2)-solar panel completely drives the 160 kW chiller during the charging period, with about 23% of solar thermal energy stored in the PCM tank. During the discharging period, the PCM tank maintains a stable cooling power of 160 kW.
The use of solar energy for cooling processes is advantageous for reducing the energy consumption of conventional air-conditioning systems and protecting the environment. In the present work, a solar-powered cooling system with parabolic trough collectors (PTC) and a phase change material (PCM) tank is numerically investigated in the arid climates of Saudi Arabia. The system contains a 160-kW double-effect absorption chiller powered by solar-heated pressurized water as a heat transfer fluid (HTF) and a shell and tube PCM as a thermal battery. The novelty of this paper is to investigate the feasibility and the potential of using a PTC solar field coupled to a PCM tank for cooling purposes in arid climates. The numerical method is adopted in this work, and a dynamic model is developed based on the lumped approach; it is validated using data from the literature. The functioning of the coupled system is investigated in both sunshine hours (charging period) and off-sunshine hours (discharging period). The PTC area in this work varies from 200 m(2) to 260 m(2) and the cooling capacity of the chiller ranges from 120 kW to 200 kW. Obtained results showed that the 160-kW chiller is fully driven by the 240 m(2)-solar PTC during the charging period and about 23% of solar thermal energy is stored in the PCM tank. It was demonstrated that increasing the PTC area from 220 m(2) to 260 m(2) leads to a reduction in the PCM charging time by up to 45%. In addition, it was found that an increase in the cooling loads from 120 kW to 200 kW induces a decrease in the stored thermal energy in the PCM tank from 450 kWh to 45 kWh. During the discharging period, the PCM tank can continue the cooling process with a stable delivered cooling power of 160 kW and an HTF temperature between 118 degrees C and 150 degrees C. The PCM tank used in the studied absorption chiller leads to a reduction of up to 30% in cooling energy consumption during off-sunshine hours.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据