4.7 Article

CFD analysis of the air supply rate influence on the aerosol dispersion in a university lecture room

期刊

BUILDING AND ENVIRONMENT
卷 235, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2023.110257

关键词

Airborne transmission; CFD analysis; Eulerian-Lagrangian model; Classroom; Ventilation; Air Change per Hour (ACH)

向作者/读者索取更多资源

The study investigates the distribution of airborne droplets (aerosol) emitted in a lecture room during a 2-hour speaking activity, as a function of different air supply rates from the HVAC system. The results show that increasing the air supply rate does not always effectively reduce aerosol concentration around the classroom seats.
The airborne droplet route has been recognized as the main pathway of infection transmission in indoor envi-ronments, drawing the attention to a proper design of Heating, Ventilation and Air Conditioning (HVAC) sys-tems. This is particularly relevant for gathering spaces such as schools and universities, due to the high crowding levels and the long exposure times. Using 3D Computational Fluid Dynamics (CFD) numerical simulations based on a Eulerian-Lagrangian approach and validated against velocity measurements, the present study investigates the distribution over time of airborne droplets (aerosol) emitted in correspondence of the teacher position inside a lecture room, during a 2-h speaking activity (so reproducing a 2-h lesson), as a function of different air supply rates from the HVAC system. As the aim of the paper is to provide useful information for proper design and operation of HVAC systems, the room has been assumed to be empty. Results show that increasing the air supply rate is not always an effective solution to reduce aerosol concentration in correspondence of the positions occupied by the students attending the lesson. In fact, for the specific case under investigation, the aerosol concentration around the classroom seats does not always decrease when increasing the supply rates, even though the overall number of particles in the room decreases. This behaviour is mainly due to the asymmetric disposition of the seats with respect to the diffusers and extraction grilles, and underlines the importance of CFD approaches in investigating the fluid dynamics in indoor environments.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据