4.7 Article

Experimental and numerical study of the thermal response of a diesel fuel tank exposed to fire impingement

期刊

APPLIED THERMAL ENGINEERING
卷 227, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2023.120334

关键词

Fuel tank; Fire engulfment; CFD modeling; Filling level; Thermal stratification

向作者/读者索取更多资源

In this study, a fire test was conducted on an 80 L fuel tank filled with diesel to a certain capacity, and a three-dimensional computational fluid dynamics (CFD) model was developed to predict the pressurization rate and temperature distributions in the tank. The results showed that the temperature stratification diminished with increasing filling level and the liquid phase was isothermal due to convection. The high filling level slowed down the pressurization of the fuel tank. The combined experimental and numerical analysis provides valuable guidance for the design of thermal protection systems and fire risk management of fuel tank explosions.
Fire exposure of diesel fuel tanks can lead to catastrophic accidents. In this study, a fire test was conducted with an 80 L cuboid fuel tank filled to 18% capacity with diesel. More importantly, an innovative three-dimensional computational fluid dynamics (CFD) model was developed aiming at predicting fuel tanks pressurization rate and temperature distributions in the inner fluid. The CFD model was verified using the experimental data and the result showed close agreement. Then, the attention was focused on the influence of different fire engulfment zones and filling levels on the thermal response of the diesel fuel tank. The results indicated that, when fire engulfed the bottom and sides of the diesel fuel tank, temperature stratification appeared in the vapor space and gradually diminished with increasing filling level; however, the liquid phase could be considered isothermal, which was dominated by the convection at the bottom. Additionally, the high filling level caused the pressuri-zation of the fuel tank to slow down due to the absence of temperature stratification in the liquid phase. The combined experimental and numerical analysis can offer valuable guidance for improve the design of thermal protection systems and the fire risk management of fuel tank explosions.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据