4.6 Article

Numerical Analysis of Heat Transfer Behaviours of Melting Process for Ice Thermal Storage Based on Various Heat Source Configurations

期刊

SUSTAINABILITY
卷 15, 期 1, 页码 -

出版社

MDPI
DOI: 10.3390/su15010365

关键词

ice thermal storage; natural convection; heat flow density; density inversion

向作者/读者索取更多资源

The influence of natural convection on the melting process of phase change material (PCM) in a shell-and-tube latent heat storage (STLHS) unit is studied numerically. The study investigates different heat source positions and configurations, and reveals that the circulation vortex formed by natural convection is a dominant factor that affects melting front evolution and the overall heat transfer coefficient. Results show that the heat transfer coefficient decreases sharply in the early stage of melting, but tends to be constant afterward. The STLHS unit with a lower heat source position and a vertical flat-tube configuration demonstrates desirable performance.
Ice thermal storage (ITS) performance for cooling systems is greatly influenced by the poor thermal conductivity of phase change material (PCM). The effect of natural convection on the melting process is significant for heat transfer enhancement. Thus, the melting performance of PCM in a shell-and-tube latent heat storage (STLHS) unit is numerically studied by considering natural convection in terms of various heat source positions and configurations, i.e., central position, eccentric position, and flat-tube type. Temperature distribution, melting time, and the overall heat transfer coefficient during the process are investigated. The results show that the circulation vortex formed by natural convection is a dominant factor that affects melting front evolution and the overall heat transfer coefficient. When input heat flux is relatively weak, PCM below the heat source is liquefied first. In contrast, PCM in the upper part melts earlier when the heat flux is excellent. The overall heat transfer coefficient decreases sharply with the increase in melting time in the early stage. Then, the heat transfer coefficient tends to be constant. PCM in an STLHS unit with a heat source in a lower position and a configuration of vertical flat-tube type has a desirable performance when compared with other cases, which could provide good support for ITS application.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据