4.5 Article

Improved models of failure time for atmospheric tanks under the coupling effect of multiple pool fires

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.jlp.2022.104957

关键词

Atmospheric storage tank; Pool fire; Coupling effect; Failure time; Domino effect

向作者/读者索取更多资源

Fire accidents in chemical installations can lead to domino effects in atmospheric tank farms storing or processing hazardous substances. Pool fires are a major cause of these accidents, and the primary hazard in domino accidents is the thermal radiation from pool fires. Previous research has focused on the escalation of domino accidents caused by a single pool fire, but this study investigates the failure of a storage tank under the coupling effect of multiple pool fires in terms of spatial and temporal synergistic processes. The study analyzes the scenario of two-pool fires, which accounted for 30.6% of pool fires according to historical accident statistics. The thermal response and damage of a target tank heated by pool fires were investigated numerically. The results showed that the temperature rise rate of the target tanks under multiple pool fires was higher, and the failure time of the tank under the coupling effect of multiple fires was lower compared to the superposition of multiple fires without the first stage. A model for the failure time of the tank under the coupling effect of pool fires was established and verified, showing better deviation than Cozzani's model.
Fire accidents of chemical installations may cause domino effects in atmospheric tank farms, where a large amount of hazardous substances are stored or processed. Pool fire is a major form of fire accidents, and the thermal radiation from pool fire is the primary hazard of domino accidents. The coupling of multiple pool fires is a realistic and important accident phenomenon that enhances the propagation of domino accidents. However, previous research has mostly focused on the escalation of domino accidents induced by a single pool fire. To overcome the drawback, in this study, the failure of a storage tank under the coupling effect of multiple pool fires was studied in view of spatial and temporal synergistic process. The historical accident statistics indicated that the accident scenario of two-pool fires accounted for 30.6% in pool fires. The domino accident scenario involving three tanks is analyzed, and the typical layout of tanks is isosceles right triangle based on Chinese standard GB50341-2014. The thermal response and damage of a target tank heated by pool fires were numerically investigated. The volume of 500 m3, 3000 m3, 5000 m3 and 10000 m3 were selected. Flame temperature was obtained by FDS, and then was input onto the finite element model. The temperature field and stress field of target tanks were simulated by ABAQUS. The results showed that the temperature rise rate of the target tanks under multiple pool fires was higher than that under a single pool fire. The failure time of the tank under the coupling effect of multiple fires was lower than that under the superposition of multiple fires without the first stage. The stress and yield strength were compared to judge the failure of the target tank. The model of failure time for the tank under the coupling effect of pool fires was established. Through the verification, the deviation of this model is 4.02%, which is better than the deviation of 15.76% with Cozzani's model.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据