4.6 Article

Fault locating and severity assessment for power distribution systems based on elasticity network topology mapping

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijepes.2022.108570

关键词

Power distribution network; Fault location; Elasticity network; Topology mapping; Fault severity assessment

向作者/读者索取更多资源

A novel method for fault locating and severity assessment in power distribution systems is proposed based on elasticity network mapping. By comparing the normalized distribution rate values, the fault location and severity can be accurately evaluated.
Although fault locating in power distribution systems has been widely studied, very few research works consider fault severity assessment, i.e., fault influence on other lines. The main reason behind this is the lack of a unified standard to quantify and assess the severity of different type of faults. In this paper, a novel power distribution system fault locating and severity assessment method is proposed based on elasticity network mapping. The principle of the proposed method is based on elastic coefficient, which reflects the state of the elastic spring by its numerical value. The partial derivative of distribution line power flow to its phase difference, denoted as dis-tribution rate (DR), is analyzed to map the line fault occurrence to the numerical change in DR. Besides, the method normalizes the DR values of different distribution lines into standardized values between 0 and 1, so that normalized comparison can be achieved. Because DR value is inversely proportional to the severity the fault, by comparing the DR of each line, the fault location and severity can be accurately evaluated. Simulation tests are performed in 10 different test feeders with around 35% of nodes installed with measurement units, reporting a 99% accuracy.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据