4.6 Article

An Error Correction Method for PD Apparent Charge Measurement in Power Transformers

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 37, 期 6, 页码 5461-5464

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2022.3188448

关键词

Transformer winding; apparent charge; PD localization; IEC60270 standard; gray-box modeling

向作者/读者索取更多资源

This study proposes a partial discharge measurement method based on frequency-spectrum-based PD localization and apparent charge error correction. By modeling the winding RLC ladder network and utilizing FRA results and intelligent algorithms, the method reduces the error in apparent charge estimation. Experimental results show that the method reduces the error by 70% in real windings.
When partial discharge (PD) measurement is performed on power transformers under the IEC60270 standard, a large error will occur in apparent charge estimation due to the winding distributive longitudinal capacitances and unknown location of the PD source. A frequency-spectrum-based PD localization and an apparent charge error correction method are proposed based on winding RLC ladder network gray-box modeling with FRA results and intelligent algorithm. An experiment on a 220 kV inhomogeneous model winding is carried out and the proposed method is applied. The results show that the maximum error of apparent charge has reduced from 37.7 dB to less than 3 dB which shows an error decrease of 70%, verifying the feasibility of this method on real windings. The proposed method requires only single-end PD measurement and follows strictly the IEC60270 standard, which is hopefully to be extended to more complex transformer windings in future research.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据