Combining direct ground cooling with ground-source heat pumps and district heating: Borehole sizing and land area requirements

期刊

GEOTHERMICS
卷 106, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.geothermics.2022.102565

关键词

Direct ground cooling; Ground -source heat pump (GSHP); Ground heat exchanger; Borehole sizing; Optimization; Cold climates

资金

  1. Swedish Energy Agency (Energimyndigheten)

向作者/读者索取更多资源

This study examines the potential combination of direct ground cooling with district heating and ground source heat pumps, comparing the required borehole depths and drilling areas. The findings indicate that the combination of direct ground cooling and district heating requires shorter borehole depths and also provide insights into optimizing investment costs and drilling areas.
This article studies the potential combination of direct ground cooling (DGC) with district heating (DH) and ground source heat pumps (GSHP) to compare the required borehole depths and needed drilling areas. It also examines two different borehole sizing approaches to optimize investment costs and drilling areas. The results show that the required borehole depths in most cases are shorter for the DGC and DH combination than for the DGC and GSHP combination. It is also demonstrated that the optimal range of borehole outlet temperatures could be chosen based on the trade-off between borehole installation and terminal units' costs.