Experimental investigation of the effects of a sidewall and cable arrangement on a horizontal cable tray fire in an open atmosphere

期刊

FIRE AND MATERIALS
卷 47, 期 5, 页码 718-732

出版社

WILEY
DOI: 10.1002/fam.3114

关键词

cable arrangement; cable tray fire; FLASHCAT model; PVC; sidewall

向作者/读者索取更多资源

This work investigates the influence of sidewalls and cable arrangements on the behavior of fire in horizontal cable trays. Large-scale fire tests and simulations were conducted to analyze the effects. The presence of a sidewall increased the fire heat release rate, while a tight cable arrangement reduced it. The results were in agreement with the predictions of the FLASHCAT model.
The work deals with the influence of a sidewall and cable arrangement on the behavior of a fire involving horizontal cable trays in the framework of fire safety assessments in nuclear installations. The analysis is based on large-scale fire tests performed in the open atmosphere in the frame of the OECD Nuclear Energy Agency (NEA) PRISME 3 project and on the corresponding simulations applying the FLASHCAT model for predicting the fire heat release rate. The fire configuration consists of five horizontal trays filled with PVC-insulated power cables. The parameters investigated are the presence or absence of a sidewall and the cable arrangement (loose or tight bundles). The results show that the presence of a sidewall increases the fire HRR in comparison to a scenario without a sidewall. This effect is due to the increase of the flame spread velocity on the lower trays. Regarding cable arrangement, a tight configuration in bundles reduces the fire HRR in comparison to a scenario with a loose arrangement. This result is due to the reduction of the fire heat release rate per unit of area (HRRPUA) as well as the flame spread velocity. The performance of the FLASHCAT model in predicting the effects of the sidewall and the cable arrangement was also assessed on the basis of the fire tests and satisfactory agreements are reported. The presented analysis demonstrates that the fire scenario with horizontal cable trays against a sidewall and with a loose cable arrangement represents a conservative scenario for fire risk assessment. In addition, on the basis of these experiments, the effect of cable arrangement is more substantial than the sidewall effect.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.2
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据