4.7 Article

Micro-characteristics of a naturally ventilated classroom air quality under varying air purifier placements

期刊

ENVIRONMENTAL RESEARCH
卷 217, 期 -, 页码 -

出版社

ACADEMIC PRESS INC ELSEVIER SCIENCE
DOI: 10.1016/j.envres.2022.114849

关键词

Classroom air quality; Air purifiers; Thermal comfort; School ventilation; Technological interventions; Children exposure

向作者/读者索取更多资源

A naturally-ventilated operational classroom was monitored to assess the spatial variations of classroom air pollution, thermal comfort, and ventilation indicators under different scenarios. The study found that CO2 and PM10 concentrations varied over time rather than space. Two air purifiers were most effective when placed in the most polluted area of the classroom. This study provides high-resolution data for validating detailed numerical models and informing decision-making to reduce children's exposure to air pollution and re-breathed CO2.
A naturally-ventilated operational classroom was instrumented at 18 locations to assess spatial variations of classroom air pollution (CRAP), thermal comfort and ventilation indicators under 10 different scenarios (base scenario without air purifier (AP); three single AP scenarios; three scenarios with two APs at same locations; three scenarios with two APs at different locations). Unlike PM2.5, monitored PM10 and CO2 concentrations followed the diurnal occupancy profile. Highest vertical variation (38%) in CO2 was at the classroom entry zone at 40-300 cm height. CO2 increased until 225 cm before stratifying further. PM10 increased to highest levels at children sitting height (100 cm) before decreasing to adult breathing height (150 cm). Highest horizontal var-iations in CO2 (PM10) were 29% (22%) at 40 cm height between the entry and occupied zones. Teachers' exposure to CO2 (PM10) in breathing zone varied by up to 6% (3%); the corresponding variations across monitored locations were up to 14% (19%). Teachers' exposure to CO2 was up to 13% higher than that of children and 18% lower for PM10. Traffic emissions (PM2.5 and NOx), secondary pollutants (VOCs and O3), thermal comfort parameters and noise level in the classroom varied insignificantly among scenarios. PM10 reduction was not doubled by using two air purifiers, which were most effective when placed within the highest PM concentration zone. Cross-comparisons of scenarios showed: use of AP reduced classroom's spatial average PM10 up to 14%; PM10 was reduced by increasing the AP's filtration capacity; and AP had insignificant impact on spatial average CO2. PM10 showed a maximum reduction of 46% (teacher zone), 62% (occupied zone) and 50% (entry zone) at children's breathing height, depending on usage scenario. This study produced high-resolution data for validating the detailed numerical models for classrooms and informing decision-making on AP's placement to minimise children's exposure to CRAP and re-breathed CO2.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据