Effect of vacuum scheme on radiative sky cooling performance

期刊

APPLIED THERMAL ENGINEERING
卷 219, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2022.119657

关键词

Radiative cooling; Vacuum; Stagnation temperature; Cooling power

向作者/读者索取更多资源

The low cooling power density hinders the wider promotion of radiative sky cooling (RSC) technology. The use of vacuum structures has been proposed to reduce non-radiative cooling loss and improve cooling capacity. However, there is a lack of comprehensive research on the effect of the vacuum mechanism on RSC performance.
Relatively low cooling power density is one of the main barriers to wider promotion of radiative sky cooling (RSC) technology. Vacuum scheme has been proposed to minimize the non-radiative cooling loss and thus improve the cooling capacity. However, systematic research to elucidate the effect of the vacuum mechanism on the RSC performance is still lacking. Therefore, in the present study, an RSC module with four vacuum structures is proposed to evaluate the performance variation resulting from the vacuum scheme. A quasi-steady state mathematical model is developed to characterize the cooling performance of the four RSC modules under different operation conditions. Results suggested that the vacuum strategy can further elevate the cooling ca-pacity if the typical RSC (TRSC) module itself can realize all-day sub-ambient cooling. However, if the TRSC cannot achieve sub-ambient cooling during peak sun hours, the vacuum scheme will deteriorate rather than ameliorate the cooling performance. On a typical summer day in Shanghai, vacuumization in both cavities en-ables a further temperature reduction of 10.21 degrees C during the nighttime, but this value decreases to only 3.39 degrees C during the daytime. The cooling power enhancement resulting from the vacuum scheme is limited in real-world dynamic operation with the thermal carrier. At a reasonable temperature gap of 5 degrees C between the emitter and ambient air, the extra cooling gain is less than 5.10 W/m2. Hence, considering the addition of energy con-sumption and system complexity caused by the vacuum unit, it may not be advisable to pursue better cooling performance of a stand-alone RSC collector/system through introducing a vacuum strategy, unless realizing a deep stagnation emitter temperature is targeted.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据