Reducing PM10 and PM2.5 Concentrations in a Subway Station by Changing the Diffuser Arrangement

期刊

TOXICS
卷 10, 期 9, 页码 -

出版社

MDPI
DOI: 10.3390/toxics10090537

关键词

particulate matter; PM10; PM2.5; subway station; indoor air quality; diffuser arrangement

资金

  1. Subway Fine Dust Reduction Technology Development Project of the Ministry of Land Infrastructure and Transport [22QPPW-C152306-04]

向作者/读者索取更多资源

This study analyzes the PM concentrations in a subway station in Seoul, Korea, considering the arrangement of air-conditioning diffusers and filtration efficiency. The findings provide recommendations for improving air quality in other subway stations.
According to the stringent regulations on particulate matter (PM) concentrations in Seoul, Korea, the PM10 and PM2.5 concentrations in subway stations must be maintained below 50 and 30 mu g/m(3), respectively, by 2024. Therefore, the PM concentrations in a subway station were analyzed considering air-conditioning diffuser arrangement and filtration efficiency, with the total ventilation flow rate of the station maintained constant. Dynamic analysis was performed under a worst-case scenario, wherein outdoor air was introduced through ground entrances and high-concentration dust (PM10, PM2.5) was introduced from stationary train cabins into the platforms through open platform screen doors (PSDs). Although the average PM concentrations were predicted to satisfy the reinforced criteria of Seoul under the existing operating conditions, the recommended limits were exceeded in certain local areas. To address this, the PM concentrations were predicted by changing the diffuser arrangement in the waiting room and maintaining the total ventilation flow rate constant. When the diffusers were placed near the waiting room walls, the PM10 and PM2.5 concentrations were reduced by approximately 10.5 and 5%, respectively, compared to the previous diffuser arrangement. Thus, the required PM concentration criteria were satisfied in nearly all areas of the target station, except for certain areas close to PSDs. The study findings can form the basis for improving the air quality of other subway stations.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据