4.7 Article

An optimal control method for small-scale GSHP-integrated air-conditioning system to improve indoor thermal environment control

期刊

JOURNAL OF BUILDING ENGINEERING
卷 59, 期 -, 页码 -

出版社

ELSEVIER
DOI: 10.1016/j.jobe.2022.105140

关键词

Ground-source heat pump; Optimal control; Room temperature control; Energy-efficiency

资金

  1. National Science Foundation of China [51178201]

向作者/读者索取更多资源

This study proposes an optimal control method to improve the control robustness of room temperature in a ground-source heat pump and air-conditioning system for villas. By calculating and adjusting the chilled-water return temperature, the control performance of indoor temperature is enhanced. The test results show good temperature control performance and reduced energy consumption.
ON/OFF controlled ground-source heat pump (GSHP) is often integrated with small-scale central air-conditioning system (ACS) for villas. Chilled-water temperature (CHWT) in this system usually oscillates in a large range due to the ON/OFF switch of the compressor. As it may be too high or too low, the cooling output of the air-handling unit (AHU) in its adjustable range may not be coincident with the indoor cooling demand, which may lead to unsatisfactory room temperature control performance. This study proposes an optimal control method for this system to improve the control robustness of the room temperature. Usually, the variation of indoor cooling-load is transferred to the chilled-water resulting in changing water temperature. In this method, the optimal chilled-water return (CHWR) temperature is calculated on the basis of the estimated sensible heat load and total cooling-load of the concerned rooms. Then, this CHWR temperature is reset following up the ON and OFF states of the compressor to regulate the variation range of the CHWT. Thus, the cooling output of the AHU in its adjustable range can always follow up the changing of indoor cooling demand. This method is tested on a simulation platform and a real ACS. The test results show good temperature control performance can be achieved. The experimental results demonstrate that the maximum deviation of room temperature is reduced by 2 degrees C and the energy consumption of the GSHP and fan can be reduced by 30.12% at light cooling-load. The application performance shows this method can be easily realized in a common building automation system.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据