4.3 Article

Electrical Life of Vacuum Interrupters for Load Current Switching

期刊

IEEE TRANSACTIONS ON PLASMA SCIENCE
卷 50, 期 9, 页码 2642-2651

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPS.2022.3175240

关键词

Contacts; Short-circuit currents; Circuit breakers; Vacuum arcs; Switching circuits; Switches; Standards; Circuit breaker; contact erosion; contactors; load current; vacuum interrupter (VI)

向作者/读者索取更多资源

Vacuum interrupters have a very long electrical life, with minimal contact erosion and good insulation and switching performance when the vacuum arc is naturally diffuse.
While the short-circuit current of vacuum interrupters (VIs) is a key performance parameter, very high current operations rarely occur in actual applications. In contrast, switching load and/or capacitive currents comprise virtually all the practical operations. Load current switching requires a low contact erosion and low metal vapor generation of the arc to achieve a long electrical life and is achieved by contacts in vacuum. However, the excellent performance of contacts in vacuum makes the testing and determination of the ultimate electrical life at load currents challenging. Tests on Cu-Cr and Cu-W contacts in VIs were performed at 2500-2700 A rms with 20,000-30,000 switching operations. The VIs with both types of contacts retained their dielectric strength, contact shape and composition, and low contact resistance. Even after arcing operations with total transferred charges >200 kA,center dot,s per interrupter, the contacts could continue providing good dielectric and switching performance with low resistance. Contact erosion was minimal and of limited practical significance. These results demonstrate the very long electrical life of VIs when the vacuum arc is naturally diffuse.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.3
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据