4.7 Article

Use of recirculated air curtains inside ventilated rooms for the isolation of transient contaminant

期刊

ENERGY AND BUILDINGS
卷 273, 期 -, 页码 -

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2022.112407

关键词

Air curtain; Recirculation; Ventilation; Protected zone; Healthy indoor environment

资金

  1. National Natural Science Foundation of China [51878043]
  2. Beijing Natural Science Foundation [8212012]
  3. Special Fund of Beijing Key Laboratory of Indoor Air Quality Evaluation and Control [BZ0344KF21-01]
  4. Fundamental Research Funds for the Central Universities [FRF-TP-20-001A3]

向作者/读者索取更多资源

This study investigated the effect of a recirculated air curtain on transient contaminant transport in a room with diluted ventilation. The results showed that adding a recirculated air curtain significantly reduced pollution in the protected zone, with the optimal discharge air velocity and air intake position affecting the containment effect.
An air curtain is an aerodynamic barrier for regional isolation and protection; however, research on its application in ventilated rooms is insufficient. This study investigated the effect of a recirculated air curtain on transient contaminant transport when used inside a room with diluted ventilation. The effects of the discharge air velocity, air intake position, and air curtain position were studied using a numerical method. The results were compared with those of diluted ventilation only. The results showed that even when the air curtain recirculated the polluted indoor air, adding a recirculated air curtain based on traditional ventilation significantly reduced the pollution in the protected zone. The containment effect on pollution initially increased and then decreased as the discharge air velocity of the air curtain increased from 0.5 to 4 m/s. A moderate velocity of 1 m/s for a jet width of 0.06 m acted as an effective aerodynamic barrier, with the average concentration in the protected zone reduced by up to 66 % at 600 s. The air intake of the air curtain strengthened the deflection of the air supply jet and vortex in the region. The air curtain exhibited better performance when the air was recirculated from the floor below it. Reducing the protected area did not significantly improve the regional protection capacity. This study guides the joint design of air curtains and air distribution patterns in healthy indoor environments.(c) 2022 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据