Unlocking demand response in commercial buildings: Empirical response of commercial buildings to daily cooling set point adjustments

期刊

ENERGY AND BUILDINGS
卷 278, 期 -, 页码 -

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2022.112599

关键词

Commercial building flexibility experiments; Data -driven building energy models; Thermal demand response; Temperature set point experiments; Commercial HVAC flexibility potential; Grid -interactive efficient buildings

向作者/读者索取更多资源

Buildings account for more than half of global electricity demand, with cooling buildings already representing over 9% of global electricity demand and expected to grow rapidly. Commercial buildings in the US consume 35% of the country's electricity, and increased cooling services demand will strain power grids during peak times. This study explores the potential of HVAC systems in commercial buildings to provide flexibility and respond to demand, based on measurements from six buildings. Adjusting temperature set points resulted in energy demand reductions, while maintaining temperatures within target ranges. This work provides a blueprint for building-level energy-response functions and highlights the importance of testing buildings under different weather conditions.
Buildings represent over half of global electricity demand. Cooling buildings already accounts for over 9% of global electricity demand and is expected to grow rapidly due to climate-change induced hot-spells and increasing prosperity in developing economies. In the US, commercial buildings represent 35% of nationwide electricity consumption. Increased electricity demand for cooling services will challenge already stressed power grids, particularly during times of peak demand. This work explores the flexibility and demand response potential of large Heating, Ventilation and Air Conditioning (HVAC) systems based on an extensive set of measurements from six commercial buildings in a Warm-summer Mediterranean climate. Over a three-month summer period, zone-level temperature set points were adjusted daily in six commercial buildings to determine the effect on chilled water and electricity loads, as well as on zonelevel temperatures. External weather conditions were measured continuously during the testing period. The experimental data that were collected are published with this article. These experiments confirmed the potential to provide flexibility by reducing energy demands based on modest zone-level temperature set point adjustments. A two-degree Fahrenheit increase of the cooling set point resulted in a 13-28% reduction in daily building-level cooling loads on average for four office buildings and 3-4% for two laboratory buildings. The impact on electric loads was less than 2% (excluding for cooling water but including for ventilation). Zone-level temperature increases were measurable but temperatures remained within the target ranges. By collecting 385 experiment-days of experiment data, we were able to parameterize statistical models for the response of the buildings. These models provide statistical guarantees on the reliability of thermal demand response. This work provides a blueprint for constructing building and zone-level energy-response functions and highlights the value of testing buildings repeatedly and across a range of weather conditions. Providing statistical performance guarantees will be critical for widespread adoption of demand response technology to provide the flexibility needed to meet peak electricity demands. Combined with thermal storage, the daily flexibility studied here would also unlock daily and sub-daily electrical flexibility, and can also be integrated with sub-daily flexibility from building-level electrical loads.(c) 2022 The Author(s). Published by Elsevier B.V. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据