期刊
CASE STUDIES IN THERMAL ENGINEERING
卷 36, 期 -, 页码 -出版社
ELSEVIER
DOI: 10.1016/j.csite.2022.102202
关键词
CFD; Coupled hybrid modelling; Tunnel ventilation; Tunnel fires; FDS; Full-scale tests
资金
- Society of Fire Protection Engineer (SFPE) Foundation
- Institute for Research in Technology (IIT) of Comillas Pontifical University
- Instytut Techniki Budowlanej (ITB)
This paper presents the validation of a coupled hybrid (1D/3D-CFD) modelling methodology for tunnel fires, and compares the results with full-scale fire tests. The study shows that the proposed methodology accurately predicts temperature profiles and backlayering lengths, reducing computational cost compared to a full-CFD numerical model.
This paper presents the validation of a coupled hybrid (1D/3D-CFD) modelling methodology, using FDS version 6.7.5, for the first time, with full-scale fire tests. Real fire conditions of the Runehamar tests with maximum heat release rates of 6 MW, 66 MW, and 119 MW are compared by assessing temperature profiles, centreline velocity, backlayering lengths, and maximum temperatures at different locations both upstream and downstream from the fire source. An expression to evaluate the length of the 3D domain where the fire is located is successfully assessed. Also, a pressure boundary condition at one of the portals is suggested to predict more precisely the inner flow conditions. The temperature profiles are accurately predicted with time-averaged differences lower than 20% beyond 40 m downstream from the fire source in the three tests. Furthermore, with the coupled hybrid approach, the backlayering length is estimated accurately with the fire of 66 MW and underestimated in the 6 MW and 119 MW fires, i.e. a maximum difference lower than 4% of the total tunnel length. The validated proposed methodology allows accurate predictions of temperature for tunnel fires and reduces the computational cost between 27% and 75% with respect to a full-CFD numerical model.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐