4.6 Article

System Vulnerability Analysis Simulation Model for Substation Subjected to Earthquakes

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 37, 期 4, 页码 2684-2692

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2021.3114279

关键词

Substations; Analytical models; Directed graphs; Earthquakes; Electronics packaging; MIMO communication; Computational modeling; Multi-input-multi-output system (MIMOS); substation; directed graph logic model; Monte Carlo simulation; performance indicator; vulnerability; earthquake

资金

  1. National Natural Science Foundation of China [51878508]

向作者/读者索取更多资源

This study presents a flow-based analysis model integrating the flow block diagram and state tree method to evaluate the earthquake-resistance capability of a complex multi-input-multi-output system substation. The developed directed graph logic system analysis model provides reliability indicators associated with the overall system. A case study on a practical substation demonstrates the potential of the analysis results in assisting decision-makers in seismic optimization.
To evaluate the earthquake-resistance capability of an entire substation, which is a complex multi-input-multi-output system (MIMOS) composed of many various types of electrical equipment interconnected by conductors, a flow-based analysis model integrating the merit of the flow block diagram and state tree method was introduced. Two performance indicators of a substation were defined from different stakeholders, one is the expected total power transmission capacity and the other is the power accessibility to the targeted users from the substation. And directed graph logic system analysis models were developed on the Simulink platform based on the original internal logic relationship among distributed components and the power delivery path in the substation with different function types. Afterward, the defined reliability indicators associated with the overall system under a certain seismic intensity level can be obtained by combining the seismic vulnerability curve at the equipment level through the Monte Carlo simulation method. The feasibility and accuracy of the proposed system vulnerability analysis model were verified by comparison with the analytical solution through the illustrative simple MIMOS. Then A case study on a practical 220/110 kV substation was conducted, the analysis results can assist decision-makers in seismic optimization of different retrofitting measures and distribution plans for substations.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。