Comparison of ventilation strategies in intensive care units for airborne infection control

出版社

TAYLOR & FRANCIS INC
DOI: 10.1080/15567036.2022.2088900

关键词

Infection control; local exhaust; HVAC; intensive care; COVID-19

向作者/读者索取更多资源

This study compares the infection prevention performances of three different ventilation layouts in an intensive care unit design. It finds that the local exhaust approach has the highest aerosol removal efficiency and meets the thermal comfort requirements.
Healthcare facilities are one of the most important buildings in an outbreak. With the tremendous increment of bed occupancy rates in intensive care units, cross-infection risks to healthcare workers also increase. Along with the personal and societal measures, airborne infection prevention via ventilation systems should be evaluated in detail for each design. In this study, the infection prevention performances of three different ventilation layouts inside a selected intensive care unit design, located in Gazi University Hospital, are compared. Three different ventilation strategies as conventional (head supply-feet exhaust, Case 1), switched (head exhaust-feet supply, Case 2), and local exhaust (Case 3) are evaluated with respect to their aerosol distribution characteristics, airflow patterns, and temperature distribution characteristics. As a result, aerosol removal efficiencies of conventional, switched, and local-exhaust approaches are found to be 18.7%, 68.3%, and 97.8%, respectively, whereas the temperature distribution in Case 3 may also meet the thermal comfort requirements.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.4
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据