4.8 Article

Neural network-based model predictive control system for optimizing building automation and management systems of sports facilities

期刊

APPLIED ENERGY
卷 318, 期 -, 页码 -

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2022.119153

关键词

Model predictive control; Neural networks; Energy management and optimization; Sports facilities

资金

  1. Qatar National Research Fund [NPRP12S-0222-190128]

向作者/读者索取更多资源

This study proposes a neural network-based model predictive control system for managing and optimizing the HVAC system of a sports hall. The neural network model outperforms other machine learning models and achieves significant energy reduction while improving indoor environmental quality.
Sports facilities are considered complex buildings due to their high energy demand and occupancy profiles. Therefore, their management and optimization are crucial for reducing their energy consumption and carbon footprint while maintaining an appropriate indoor environmental quality. This work is part of the SportE3.Q project, which aims to manage and optimize the operation of sports facilities. A neural network (NN)-based model predictive control (MPC) management and optimization system is proposed for the heating, ventilation, and air conditioning (HVAC) system of a sports hall in the sports and events complex of Qatar University (QU). The proposed approach provides an integrated dynamic optimization method that accounts for future system behavior in the decision-making process, consisting of a prediction element and an optimizer. A NN is used to implement the dynamic prediction element of the MPC system and is compared with other machine learning (ML)-based models, which are support vector regression (SVR), k-nearest neighbor (kNN), and decision trees (DT). The NN-based model outperforms the other ML models with an average root mean squared error (RMSE) of around 0.06 between the actual and the predicted values, and an average R of 0.99 as NNs are popular for their high accuracy and reliability. Two schemes of the proposed NN-based MPC system are investigated for managing and optimizing the operation of the hall's HVAC system for enhanced energy use and indoor environment quality, as wel l as for providing occupancy profile recommendations to aid the facilities' managers in handling their operation. In alignment with the objective of the SportE3.Q project, up to 46% energ y reduction was achieved while jointly optimizing the thermal comfort and indoor air quality. In addition, Scheme 2 of the proposed system provided productive occupancy recommendations for a healthier indoor environment.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据