4.7 Article

Heat balance modelling and simulation of non-mixing buffer tank design for hydronic heating applications

期刊

ENERGY
卷 244, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.energy.2022.123213

关键词

Hydronic heating systems; Heat balance modelling; Buffer tank; Water mixing; System design and simulation

资金

  1. NSERC Discovery Grants

向作者/读者索取更多资源

The paper aims to develop a theoretical model for a non-mixing buffer tank system in hydronic heating applications. The non-mixing design, which includes a movable separation plate in the buffer tank, allows for separate storage of supply hot water and return cold water. Simulation results show that the non-mixing design achieves better system efficiency, boiler efficiency, and cycle period compared to the mixing design. Additionally, the non-mixing design offers better control of supply water temperature, supporting outdoor reset control of boilers.
The purpose of this paper is twofold. First, it aims to develop a theoretical model for a non-mixing buffer tank system for hydronic heating applications. The traditional buffer tanks often involve water mixing where the boiler's hot water is mixed with the system's return water. This practice reduces the tem-perature differences (DT) through the boilers and the in-space heating equipment, bringing in concerns of their thermal performance. To address this concern, the non-mixing buffer tank system is designed with a movable separation plate in a buffer tank, which can store supply hot water and return cold water separately. The theoretical model of the non-mixing design explores the dynamics of water temperatures and the interactions of system components. As the second purpose, this paper then conducts a simu-lation study to compare both mixing and non-mixing designs under the same heating loads. As a result, it is observed that the non-mixing design can achieve better system efficiency (e.g., 86.7% versus 82.0% for low heating loads) due to better average boiler's efficiency (90.5% versus 86.8%) and longer cycle period (37.85 min vs. 9.27 min). In addition, the non-mixing design allows better control of supply water temperature, which can better support the outdoor reset control of boilers.(c) 2022 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据